G50 Serie LN: 50kA 10 / 350 μs
G100/xxxNPE: Max 100kA 10/350 μs
50kA Klassee I / Type 1 Surge Protection Device (SPD) Funktiounen
- Net-Pluggable T1 + 2 SPD mat Encapsulated Spark Gap (ESG) Technologie fir d'Zouverlässegkeet an de robusten Ëmfeld an d'exposé de location exposition
- Helle Blitzschnouer ofléisen Kapazitéit bis Iimp 50kA 10 / 350μs
- Degradatiounsindikatioun & optional Remote Signal Kontakt
- Low Voltage Protection Level
- Fëllt mat IEC / EN 61643-11, UL 1449 4th, IEEE C62.41, CSA C22.2
50kA Klassee / Typ 1 Surge Protection Device (SPD) Spec
Modell | G50 / 150-S | G50 / 175-S | G50 / 275-S | G50 / 320-S | G50 / 385-S | G50 / 420-S | |
Compliance | EN / IEC 61643-11 | ||||||
Kategorie IEC / EN | Klasse I + II / T1 + 2 | ||||||
Max. Kontinuier Operatioun Voltage (AC) | Uc | 150V | 175V | 275V | 320V | 385V | 420V |
Technology | ESG Technologie Thermesche Trennung | ||||||
Ports / Protection Mode | 1 / L-PE oder LN oder N-PE | ||||||
Lightning Impulse Stroum (10 / 350μs) | Iimp | 50kA | |||||
Nominal Entlëschter Stroum (8 / 20μs) | In | 50kA | |||||
Max. Entlëschter Stroum (8 / 20μs) | Imax | 150kA | |||||
Voltage Protection Level | Up | ≤1.2kV | ≤1.2kV | ≤1.5kV | ≤1.6kV | ≤1.8kV | ≤2.0kV |
Temporärer Overvoltage TOV -Wennstand Modus | Utov ageholl | 228V / 120min | 228V / 120min | 442V / 120min | 442V / 120min | 529V / 120min | 585V / 120min |
Residualsäit | kuerz | Nee | |||||
Neit aktuelle Interrupt Rating | Wann ech | 25kA | |||||
Kurzfristeg Aktuellt Rating per IEC 61643-11 | Isc | 25kA | |||||
Response Time | tA | ≤100ns | |||||
Backup Fuse (nëmmen wann net schon am Netz geliwwert gëtt) | 500A gL / gG | ||||||
Emwelt | Temperaturberäich: - 40ºC ~ + 85ºC; Fiichtegkeet: ≤95%; Héicht: ≤2000m | ||||||
Cross-Section of Connection Wire | Eenzelsträng 35mm2; Multi-Strang 25mm2 | ||||||
Opriichte | 35mm DIN-Schiene no den EN 50022 / DIN46277-3 | ||||||
Schlaang Material | thermoplastescht Läschgrad UL94 V-0 | ||||||
Schutzgrad | IP20 | ||||||
Installatioun Breite | 2 Module, DIN 43880 | ||||||
Failure Indication / Status | RED- Failure | ||||||
Remote Alarm Kontakt | Jo | ||||||
Zertifizéierungen, Zertifizéierung | CE | ||||||
Zusätzlech Donnéen fir Remote Alarm Kontakten | |||||||
Remote Alarm Kontakttyp | Isoléiert Form C | ||||||
Kapazitéit de Kapazitéit Un / In | AC: 250V / 0.5A; DC: 250V / 0.1A; 125V / 0.2A; 75V / 0.5A | ||||||
Max. Gréisst vum verbindenden Drot | Max. 1.5 mm2 (oder # 16AWG) |
Multi-Pole Surge Protection Device Combination
Part No. | Pol | Kombinatioun | Power System | Max. Operatioun Spannung Uc | Lightning Impulse Stroum (10 / 350μs) Iimp | Voltage Protection Level Up | Diagram |
G50 / 150-S / 2P | 2 | 2 x G50 / 150-S | Eenzel Phase 2W + G | 150Vac | 50kA | L / NG: 1.2kV | 4 |
G50 / 175-S / 2P | 2 | 2 x G50 / 175-S | Eenzel Phase 2W + G | 175Vac | 50kA | L / NG: 1.2kV | 4 |
G50 / 275-S / 2P | 2 | 2 x G50 / 275-S | Eenzel Phase 2W + G | 275Vac | 50kA | L / NG: 1.5kV | 4 |
G50 / 320-S / 2P | 2 | 2 x G50 / 320-S | Eenzel Phase 2W + G | 320Vac | 50kA | L / NG: 1.6kV | 4 |
G50 / 385-S / 2P | 2 | 2 x G50 / 385-S | Eenzel Phase 2W + G | 385Vac | 50kA | L / NG: 1.8kV | 4 |
G50 / 420-S / 2P | 2 | 2 x G50 / 420-S | Eenzel Phase 2W + G | 420Vac | 50kA | L / NG: 2.0kV | 4 |
G50 / 150-S / PN50 | 2 | G50 / 150-S + G50 / 255NPE | Eenzel Phase 2W + G | 150Vac | 50kA | LN: 1.2kV, N-PE: 1.5kV | 3 |
G50 / 175-S / PN50 | 2 | G50 / 175-S + G50 / 255NPE | Eenzel Phase 2W + G | 175Vac | 50kA | LN: 1.2kV, N-PE: 1.5kV | 3 |
G50 / 275-S / PN50 | 2 | G50 / 275-S + G50 / 255NPE | Eenzel Phase 2W + G | 275Vac | 50kA | LN: 1.5kV, N-PE: 1.5kV | 3 |
G50 / 320-S / PN50 | 2 | G50 / 320-S + G50 / 255NPE | Eenzel Phase 2W + G | 320Vac | 50kA | LN: 1.6kV, N-PE: 1.5kV | 3 |
G50 / 385-S / PN50 | 2 | G50 / 385-S + G50 / 255NPE | Eenzel Phase 2W + G | 385Vac | 50kA | LN: 1.8kV, N-PE: 1.5kV | 3 |
G50 / 420-S / PN50 | 2 | G50 / 420-S + G50 / 255NPE | Eenzel Phase 2W + G | 420Vac | 50kA | LN: 2.0kV, N-PE: 1.5kV | 3 |
G50 / 150-S / 3P | 3 | 3 x G50 / 150-S | Dräi Phase 3W + G | 150Vac | 50kA | LG: 1.2kV | 2 |
G50 / 175-S / 3P | 3 | 3 x G50 / 175-S | Dräi Phase 3W + G | 175Vac | 50kA | LG: 1.2kV | 2 |
G50 / 275-S / 3P | 3 | 3 x G50 / 275-S | Dräi Phase 3W + G | 275Vac | 50kA | LG: 1.5kV | 2 |
G50 / 320-S / 3P | 3 | 3 x G50 / 320-S | Dräi Phase 3W + G | 320Vac | 50kA | LG: 1.6kV | 2 |
G50 / 385-S / 3P | 3 | 3 x G50 / 385-S | Dräi Phase 3W + G | 385Vac | 50kA | LG: 1.8kV | 2 |
G50 / 420-S / 3P | 3 | 3 x G50 / 420-S | Dräi Phase 3W + G | 420Vac | 50kA | LG: 2.0kV | 2 |
G50 / 150-S / 3PN100 | 4 | 3 x G50 / 150-S + G100 / 255NPE | Dräi Phase 4W + G | 150Vac | 50kA / 100kA (NPE) | LN: 1.2kV, N-PE: 1.5kV | 1 |
G50 / 175-S / 3PN100 | 4 | 3 x G50 / 175-S + G100 / 255NPE | Dräi Phase 4W + G | 175Vac | 50kA / 100kA (NPE) | LN: 1.2kV, N-PE: 1.5kV | 1 |
G50 / 275-S / 3PN100 | 4 | 3 x G50 / 275-S + G100 / 255NPE | Dräi Phase 4W + G | 275Vac | 50kA / 100kA (NPE) | LN: 1.5kV, N-PE: 1.5kV | 1 |
G50 / 320-S / 3PN100 | 4 | 3 x G50 / 320-S + G100 / 255NPE | Dräi Phase 4W + G | 320Vac | 50kA / 100kA (NPE) | LN: 1.6kV, N-PE: 1.5kV | 1 |
G50 / 385-S / 3PN100 | 4 | 3 x G50 / 385-S + G100 / 255NPE | Dräi Phase 4W + G | 385Vac | 50kA / 100kA (NPE) | LN: 1.8kV, N-PE: 1.5kV | 1 |
G50 / 420-S / 3PN100 | 4 | 3 x G50 / 420-S + G100 / 255NPE | Dräi Phase 4W + G | 420Vac | 50kA / 100kA (NPE) | LN: 2.0kV, N-PE: 1.5kV | 1 |
N-PE Modul Surge Protection Device (SPD) Funktiounen
- T1 + 2 SPD mat Encapsulated Spark Gap (ESG) Technologie, fir Zouhalverlässegkeet an robusten Ëmfeld an exposéierter Positioun ze garantéieren
- Helleg Blitzestrom d'Auslaagkapazitéit bis Iimp 100kA 10 / 350
- Low Voltage Protection Level
- Fëllt mat IEC / EN 61643-11, UL 1449 4th, IEEE C62.41, CSA C22.2
N-PE Modul Surge Protection Device (SPD) Spezifikatiounen
Modell | G100 / 255NPE | G50 / 255NPE | G25 / 255NPE | |
Compliance | EN / IEC 61643-11 | |||
Kategorie IEC / EN | Klasse I + II / T1 + 2 | |||
Max. Kontinuier Operatioun Voltage (AC) | Uc | 255V | ||
Technology | ESG Technologie | |||
Ports / Protection Mode | 1 / N-PE | |||
Lightning Impulse Stroum (10 / 350μs) | Iimp | 100kA | 50kA | 25kA |
Nominal Entlëschter Stroum (8 / 20μs) | In | 100kA | 50kA | 25kA |
Max. Entlëschter Stroum (8 / 20μs) | Imax | 200kA | 150kA | 100kA |
Voltage Protection Level (1.2 / 50) | Up | ≤1.5kV | ||
Temporärer Overvoltage TOV -Wennstand Modus | Utov ageholl | 1200V / 200ms | ||
Residualsäit | kuerz | Nee | ||
Neit aktuelle Interrupt Rating | Wann ech | 200A @ 255Vac | ||
Response Time | tA | ≤100ns | ||
Emwelt | Temperaturberäich: - 40ºC ~ + 85ºC; Fiichtegkeet: £ 95%; Héicht: 2000m | |||
Cross-Section of Connection Wire | Eenzelsträng 35mm2; Multi-Strang 25mm2 | |||
Opriichte | 35mm DIN-Schiene no den EN 50022 / DIN46277-3 | |||
Schlaang Material | thermoplastescht Läschgrad UL94 V-0 | |||
Schutzgrad | IP20 | |||
Installatioun Breite | 2 Module, DIN 43880 | |||
Zertifizéierungen, Zertifizéierung | CE |
Prosurge Surge Protection Device Produkter Famill
Klickt fir eis extensive Surge Protection Apparater an aner Blitzschutzprodukter ze erforschen.
DIN-Schiene SPD fir AC Energieversuergung
Panel SPD fir AC Energieversuergung
IEC Standard
UL Standard
Email Prosurge an Äntwert op 2 Stonnen
wéi kompetitiv eisen Präis ass:)
Léiert Live Chat mat eis klickt op den Chat-Knop an der rechter riets Eck
Fill d'Kontaktform an Äer Äntwert an 2 Stonnen
Fir den nordamerikanesche Maart, kuckt weg
Fir aner Mäert, da kontaktéiert weg
+ 86 757 8632 7660